Recommendation Number | Significant Recommendation | Recommended Questioned Costs | Recommended Funds for Better Use | Additional Details | |
---|---|---|---|---|---|
2 | No | $0 | $0 | ||
We recommend that OPM perform a gap analysis to identify the monitoring, inventory, and management tools that it needs to implement automated infrastructure management as required by the DCOI and OMB. | |||||
3 | No | $0 | $0 | ||
We recommend that OPM install automated power metering in all of its data centers in accordance with the requirements in the DCOI. | |||||
4 | No | $0 | $0 | ||
We recommend that OPM assess the current state of its infrastructure to accurately report data center metrics, including the correct number of data centers (including non-tiered spaces), the correct operational status of data centers, and accurate energy usage. |